The 60 GHz fall-detection module (R60AFD1-V) already decides, on its own, whether a person has fallen. It exposes that decision as a single 3.3 V logic pin — GP1 goes High the moment a fall is detected, and Low when the alarm clears. This article shows how to turn that one pin into a local audible / visual alarm with no microcontroller and no firmware: a transistor, a relay, and a buzzer. No serial parser, no broker, no network.

This is the module, not the finished Wi-Fi radar. The finished unit has no exposed GPIO; this article is for integrators building the sensor into their own product or a local alarm.

What GP1 is, exactly

Pin Level Meaning
GP1 High = fall detected, Low = clear Active-high fall alarm
GP2 High = someone present, Low = empty Occupancy (optional here)

Two hard facts about the pin:

The one rule that prevents burned boards

GP1 switches a transistor. The transistor switches the load. GP1 never touches the load.

Nearly every “it doesn’t work / the module died” case in this setup comes from skipping that rule.

Bill of materials

Qty Part Notes
1 R60AFD1-V module 60 GHz fall module, UART + GPIO
1 Logic-level N-channel MOSFET (e.g. AO3400, IRLZ44N) Gate fully on at 3.3 V. An NPN (S8050 / 2N2222) + 1 kΩ base resistor also works
1 5 V relay, or active 5 V buzzer Relay if you want a dry-contact output; buzzer for sound only
1 Flyback diode (1N4007) Required across the relay coil; not needed for a buzzer
1 10 kΩ resistor Gate pull-down, keeps the MOSFET off at boot
1 5 V supply, ≥ 500 mA Module peaks at 300 mA; ripple ≤ 100 mV
— Wires, breadboard / PCB —

If you use an NPN instead of a MOSFET, replace the 10 kΩ gate pull-down with a 1 kΩ base resistor between GP1 and the base; emitter to GND, collector to the load.

Wiring

        R60AFD1-V                       Load side (5 V)
      ┌──────────────┐
 GP1 ─┤ GP1          │
      │              │         10 kΩ        Gate
      │          GND ├───┬───────▱▱───────┤ G
      └──────────────┘   │               ├─ N-ch MOSFET (logic level)
                         │          D ────┤ D
                         │          S ────┴── GND (5 V supply −)
                         │
                   +5 V supply ──► relay coil ──► D (MOSFET drain)
                                   │
                                1N4007 (cathode to +5 V, anode to D)
                                   │
                        buzzer / NO contact ──► load ──► GND

Plain-text steps:

  1. Connect the module 5V and GND to your 5 V supply.
  2. GP1 → 10 kΩ pull-down → MOSFET gate. Tie the gate to GND through the 10 kΩ so it stays off until GP1 drives it.
  3. MOSFET source → 5 V supply GND.
  4. MOSFET drain → one end of the relay coil (or buzzer +).
  5. Other end of the coil / buzzer → +5 V.
  6. Flyback diode (1N4007) across the relay coil: cathode to +5 V, anode to the drain side.
  7. The relay’s NO (normally open) contacts switch your buzzer, siren, light, or any 5 V / 12 V load.

When GP1 goes High, the MOSFET turns on, the coil energizes, and the NO contacts close — the buzzer sounds. When the alarm clears (GP1 Low), the relay releases.

Expected behavior

Add GP2 for “only alarm when someone is present”

GP2 is High when someone is in the coverage area. You can use it to arm the alarm: feed GP2 into the relay coil’s supply path (or a second transistor) so the buzzer only sounds when a person is actually present. This prevents the relay from latching on a stale state with nobody in the room.

Power and false-alarm reality

Where to go next