PLCs and building-management systems in care homes and commercial buildings do not speak MQTT or JSON. They want a dry contact — a switch that closes. The 60 GHz fall module (R60AFD1-V) gives you exactly that opportunity through GP1 (active-high: High = fall detected). With one optocoupler you turn GP1’s 3.3 V logic into an isolated contact the PLC can read, with no microcontroller and no network in between.

This is the module, not the finished Wi-Fi radar. The finished unit has no exposed GPIO.

What GP1 is, and why isolation matters

Pin Level Meaning
GP1 High = fall detected, Low = clear Active-high fall alarm
GP2 High = someone present, Low = empty Occupancy (optional)

Two properties drive the design:

An optocoupler solves both: the radar’s GP1 drives the opto’s LED; the opto’s phototransistor switches the PLC input. The two sides share no electrical connection.

Bill of materials

Qty Part Notes
1 R60AFD1-V module 60 GHz fall module, UART + GPIO
1 Optocoupler, e.g. PC817 / LTV-817 NPN phototransistor output, VCEO ≥ 35 V
1 Resistor 220–330 Ω Limits LED current from GP1 (3.3 V)
1 Pull-up 4.7 kΩ – 10 kΩ For the PLC side, if required by the input type
1 5 V supply, ≥ 500 mA Module peaks at 300 mA; ripple ≤ 100 mV
— PLC digital input (24 V), wires Sinking or sourcing per your PLC

The phototransistor in a PC817 comfortably handles the few mA a PLC digital input draws, and its 35 V rating covers 24 V.

Wiring (sinking PLC input — the common case)

Most PLC digital inputs are sinking: they sink current from an external 24 V through the field device.

   Radar side (3.3 V)                 PLC side (24 V, isolated)
 ┌──────────────┐
 │ R60AFD1-V    │
 │ GP1 ─┐       │
 │      ├──▱▱───┤─── opto LED anode (220–330 Ω)
 │   GND ├──────┤─── opto LED cathode
 └──────────────┘         │
                    opto phototransistor
                    collector ───► 24 V (via 4.7k pull-up if needed)
                    emitter   ───► PLC digital input (Ix)
                                    PLC COM / 0V ───► 0 V

Plain-text steps:

  1. Power the module from 5 V (4.5–5.5 V, ripple ≤ 100 mV); radar GND is its own domain.
  2. GP1 → 220–330 Ω → opto LED anode; LED cathode → radar GND.
  3. Opto phototransistor collector → PLC 24 V (or through a 4.7 kΩ pull-up to 24 V, depending on the input).
  4. Opto phototransistor emitter → PLC digital input (Ix).
  5. PLC COM / 0 V → 0 V.

When GP1 goes High, the LED lights, the phototransistor conducts, and the PLC input energizes — your ladder logic sees a fall event and can trigger a call system, lighting, or HVAC. When the alarm clears (GP1 Low), the contact opens. The two grounds never connect.

If your PLC inputs are sourcing instead, swap the polarity: emitter → 0 V, collector → PLC input, and the PLC provides the 24 V internally. The opto still isolates.

Behavior and tuning

Add GP2 to arm the contact

Feed GP2 (High = someone present) into the loop so the PLC only registers a fall when a person is actually in the coverage area — preventing a stale trigger with the room empty.

Caveats

Module specifications (R60AFD1-V datasheet)

Every figure below is taken from the R60AFD1-V datasheet v2.1 (MicRadar / 云帆瑞达). Nothing here is assumed.

Interface 1 — the connector you actually use (2×3, 2.0 mm pitch):

Pin Signal Level Notes
1 5V 5.0 V Power input +
2 GND — Ground
3 RX 3.3 V TTL UART receive
4 TX 3.3 V TTL UART transmit
5 GP1 3.3 V / 0 V High = fall alarm, Low = clear
6 GP2 3.3 V / 0 V High = occupied, Low = empty

Interface 2 (2×4) is the programming/debug port: 3V3, GND, SWC, SWD, GP3–GP6. GP3–GP6 are spare and user-redefinable.

Electrical (operating):

Parameter Min Typ Max Unit
VCC 4.5 5.0 5.5 V
Average current (ICC) — — 100 mA
Peak current (Ipeak) — — 300 mA
Operating temperature −20 — +70 °C
Storage temperature −40 — +85 °C

Supply ripple must be ≤ 100 mV; the supply must deliver enough current and transient response for the 300 mA peak.

RF and detection:

Parameter Value
Frequency 61 – 62.5 GHz
Tx power 8 dBm typ, 10 dBm max
Antenna gain 8 dBi
Detection radius (motion / fall / static dwell) 1.5 m typ @ 2.8 m ceiling
Beam angle (horizontal / pitch) 100° / 100°
Motion output latency ≤ 100 ms
Nobody → nobody-absent output 10 – 60 s
Fall detection latency 5 – 20 s (15 s typ)

Install and configuration:

The key point for this article: GP1 is a 3.3 V logic output, not 24 V — which is exactly why the optocoupler is required between it and the PLC.

Where to go next

Evaluation units are on Tindie.