The 24 GHz presence module (R24AVD1) reports whether a space is occupied as a single logic pin: S1 goes High when someone is present and Low when empty. Wire S1 to a relay and you get occupancy-controlled lighting or HVAC with no Wi-Fi, no cloud, no gateway — the radar switches your load directly. This reuses the same transistor/relay topology as the fall-alarm article, applied to a lower-cost 24 GHz part.
What S1 (and S2) are
| Pin | Level | Meaning |
|---|---|---|
| S1 | High = occupied, Low = unoccupied | Presence |
| S2 | High = active (moving), Low = static | Motion vs stillness |
| GP1–GP4 | redefinable | — |
Key behaviors from the module’s protocol:
- Occupied → unoccupied is reported after a 40 s stillness delay; occupied appears in < 0.5 s.
- Sensitivity (DP5, 1–10, default 7) and scene mode (DP6) tune range and false-trigger rejection. Use a lower sensitivity in corridors/parking where curtain or plant sway would otherwise false-trigger.
- Power the module per its datasheet (3.3 V I/O; VCC and current are specified there). The relay/load side uses its own 5 V/12 V supply, kept separate from the module.
The same rule as always
S1 switches a transistor; the transistor switches the load. S1 never touches the load.
The pin is 3.3 V TTL and weak (mA-level) — never drive a relay or lamp directly.
Bill of materials
| Qty | Part | Notes |
|---|---|---|
| 1 | R24AVD1 module | 24 GHz presence module, UART + GPIO |
| 1 | Logic-level N-channel MOSFET (e.g. AO3400, IRLZ44N) | Gate on at 3.3 V; NPN + 1 kΩ also works |
| 1 | 5 V / 12 V relay (or contactor for HVAC) | Rating must exceed the load |
| 1 | Flyback diode (1N4007) | Across the relay coil |
| 1 | 10 kΩ resistor | Gate pull-down |
| 1 | Supply for the module (per datasheet) + supply for the load | Separate domains |
| — | Wires, enclosure | Non-metal, flat face; 3–5 mm from antenna to shell |
Wiring
R24AVD1 (3.3 V) Load side (5 V / 12 V)
┌──────────────┐
│ S1 ─┐ │
│ ├─▱▱─────┤── 10 kΩ pull-down ──► MOSFET gate
│ GND ├────────┤────────────────────► MOSFET source ──► load supply 0 V
└──────────────┘ MOSFET drain ──► relay coil ──► load +V
1N4007 (cathode to +V, anode to drain)
NO contacts ──► light / HVAC ──► 0 V
- Power the module from its specified supply; power the relay/load from its own 5 V/12 V supply.
- S1 → 10 kΩ pull-down → MOSFET gate.
- MOSFET source → load-supply 0 V.
- MOSFET drain → relay coil → load +V; flyback diode across the coil.
- Relay NO contacts switch the light or HVAC circuit.
When S1 is High, the relay closes and the load runs; when the space goes empty (after the 40 s delay), it opens.
Using S2 to avoid “lights off while still”
S2 is High only when the person is moving. If you drive the relay from S1 alone, a person who sits still keeps the lights on (good). If you prefer “on only while moving,” use S2 instead — but then a still person darkens the room. Most installs want S1 for occupancy and leave S2 for UART-based analytics.
Mounting and false-trigger reality
- Ceiling mount, height ≤ 2.75 m, tilt ≤ 3°, long side of the board toward the door. Keep the antenna 3–5 mm from the enclosure’s inner surface.
- Known false-alarm sources: fans, pets near the radar, swinging metal curtains, and the internal motor of an air conditioner directly in the beam. Aim the beam away from these.
- Not a medical device. A sensing building block; not for diagnosis or treatment.
Module specifications (R24AVD1 guide)
Every figure below is from the R24AVD1 getting-started guide (MicRadar / 云帆瑞达). Note: this guide does not publish VCC or current — power the module per its datasheet; the I/O levels below are the only electrical values given (all 3.3 V).
Output pins (3.3 V logic):
| Pin | High | Low | Notes |
|---|---|---|---|
| S1 | occupied | unoccupied | presence |
| S2 | active (moving) | static | motion vs stillness |
| GP1–GP4 | redefinable | — | parameter-selection control, user-redefinable |
Data points (protocol):
| DP | Function | Behavior |
|---|---|---|
| DP1 | occupied / unoccupied | unoccupied→occupied ≤ 0.5 s; occupied→unoccupied 40 s |
| DP2 | static / active | switch reported ≤ 0.5 s |
| DP3 | approach / leave / no-direction move | 2 s per report |
| DP4 | body-motion amplitude | 0–100, 5 s per report |
| DP5 | sensitivity | 1–10 (default 7) |
| DP6 | scene mode | area / bathroom / hotel / bedroom / office / max-area |
Body-motion amplitude (DP4): 0% none; 1% static (sleep, breathing only); 2–30% micro motion; 31–60% walk / slow limb; 61–100% run / large close motion.
Sensitivity bands (DP5, default 7): low (1–3) for corridor/parking — large motion only, rejects curtain/plant sway; mid (4–6) normal indoor; high (7–10) low-interference spaces — fine motion, but prone to false “occupied”.
Coverage and range (ceiling mount): beam 90° horizontal / 60° pitch. Install height ≤ 2.75 m, tilt ≤ 3°, antenna face 3–5 mm from a non-metal, flat enclosure. Detection at ceiling: motion ≈ 8 m × 12 m, static ≈ 4 m × 6 m, sleep ≈ 3 m × 2 m. Max diameters: motion 12 m, static 6 m, sleep 3 m.
Scene-mode ranges (trigger / static diameter): max-area 12/8 m & 6/4 m; office 10/7 m & 6/4 m; hotel (default) 9/6 m & 6/4 m; living 7/5 m & 6/4 m; bedroom 4/3 m & 6/4 m; area-detect 3/2 m & 6/4 m; bathroom 1.8/1.5 m & 6/4 m.
Interference (from the guide): moving non-living objects — metal/liquid motion, oscillating fans, pets near the radar, swinging metal curtains — cause false triggers. Do not aim the beam directly at an air conditioner (its internal motor false-triggers); aim parallel to it instead.
Layout: keep the radar’s components ≥ 1 mm above other PCBA parts; the enclosure face must be non-metal and flat (no curved surface).
Where to go next
- The GPIO/UART split: GPIO vs UART.
- Same topology on the fall module: Local fall alarm.
- Full specs: Module spec sheet.
- Presence tuning: Presence radar guide.